DATAFLEX LiYY
DATA CABLES (DATA CABLES)
CPR Class: Eca
APPROPRIATE USE
Flexible data transmission cable for information processing system, office machines, computer systems, suitable as measuring, control and signal cable for electronic control equipments, balances, etc. also as electronic cable in the milliampere range.
CHARACTERISTICS |
DESCRIPTION |
REFERENCE |
|
---|---|---|---|
Type of cable | LiYY | ||
Nominal Voltage | 0,14 mm2: 350V ; ≥ 0,25 mm2: 500V (not for power applications) | ||
1 | Core | Thin raw copper wires | EN 60228 |
2 | Insulation | PVC TI2 special type | EN 50363 |
3 | Sheath | PVC TM2 special type, grey colour RAL 7001 o RAL 7032 | EN 50363 |
Temperature range | Fixed laying: from -40°C to 80°C, mobile laying: from -5°C to 70°C | ||
Testing voltage | Conductor/conductor: 1500 V AC | ||
Minimum banding radius | Fixed laying: 4 x external diameter - Mobile laying: 10 x external diameter | ||
Package | 100 m thermo-shrinking material coils - Drums |
GENERAL REFERENCE
DIN VDE 0812, EN 50575:2014 + EN 50575/A1:2016
CORE IDENTIFICATION
Coloured cores (DIN 47100)