CONDORFLEX® YuYu JZ/OZ 300/500V
CONTROL CABLES (PVC CABLES - MULTI PURPOSE)
CPR Class: Cca s3, d1, a3
FIRE RETARDANT
APPROPRIATE USE
Suitable for signalling and control, installed inside proper pipes and protected ducts with special performance in reaction to the fire.
Buried laying is not allowed.
CHARACTERISTICS |
DESCRIPTION |
REFERENCE |
|
---|---|---|---|
Type of cable | YuYu JZ/OZ | ||
Nominal Voltage | Uo/U 300/500 V | ||
1 | Core | Class 5 flexible annealed red copper | EN 60228 |
2 | Insulation | PVC S17 type | EN 50363 |
3 | Sheath | PVC R18 special type, grey colour RAL 7001 (Oil Resistance TM54) | EN 50363 |
Temperature range | Occasional flexing: from -15°C to +70°C. Mobile laying: from -5°C to +70°C Fixed laying: from -40°C to +80°C | ||
Testing voltage | 4000V AC | ||
Minimum banding radius | Fixed laying: 5 x external diameter - Mobile laying: 8 x external diameter | ||
Package | 100 m thermo-shrinking material coils - Drums |
GENERAL REFERENCE
EN 50525-2-51, EN 50575:2014 + EN 50575/A1:2016
CORE IDENTIFICATION
Black cores numbered in white (EN 50334). JZ: with Yellow/Green; OZ: no Yellow/Green